Diesel Generator Sets
MGS0700R

GENERAL SPECIFICATIONS

Generator set model :
MGS0700R

Generator voltage range (V) :
380V/480V

Frequency (Hz) :
60

Duty :
see below for options

Installation location :
Indoor

Options :
Custom enclosure – Containerized

ENGINE DATA

Engine model  :
S6A3-PTAA

Engine speed (rpm)

1800

Turbocharged  : 
4 cycle, direct injection, turbocharged with air cooler

Governor  : 
Digital Electrical type

Cooling method  : 
Centrifugal type driven by engine

OPTIONS

Please select your VOLTAGE requirement then then RATING / DUTY.

Legend:

ESP: Standby
CP: Critical Power
PRP: Prime
DCCP: Data Center Continuous Power

1. Generator is 3 Phase 4 wire (star connection), Class H insulation and temperature rise 125°C (DCCP/PRP)/ 150 °C (CP/ESP).

2. Genset operating conditions is assumed 40 °C ambient temperature and altitude is 1000 meters ASL (Above Sea Level).

3. Rated Power factor is 0.8 Lagging.

1. Select

2. Select

SPECIFICATIONS

Generator set modelMGS0700R
Generator voltage (V)380
Frequency (Hz)60
Generator output (kVA)581.25
Generator output (kW)465.00
DutyStandby
Rating PrimeStandby (ESP)
Average load factor for 24h– Maximum 80%
– 100% in emergency
OverloadNot available
Installation locationIndoor

ENGINE DATA

Engine modelS6A3-PTAA
Engine speed (rpm)1800
Engine brake output (kWm)536.00
Turbocharged4 cycle, direct injection, turbocharged with air cooler
GovernorDigital Electrical type
Cooling methodCentrifugal type driven by engine
Starting methodStarter motor capacity : 7.5kW x 2 (DC24V)

SPECIFICATIONS

Generator set modelMGS0800R
Generator voltage (V)380
Frequency (Hz)60
Generator output (kVA)775.00
Generator output (kW)620.00
DutyStandby
Rating PrimeStandby (ESP)
Average load factor for 24h– Maximum 80%
– 100% in emergency
OverloadNot available
Installation locationIndoor

ENGINE DATA

Engine modelS6R-PTAR
Engine speed (rpm)1800
Engine brake output (kWm)688.00
Turbocharged4 cycle, direct injection, turbocharged with air cooler
GovernorDigital Electrical type
Cooling methodCentrifugal type driven by engine
Starting methodStarter motor capacity : 7.5kW x 2 (DC24V)

SPECIFICATIONS

Generator set modelMGS0700R
Generator voltage (V)380
Frequency (Hz)60
Generator output (kVA)512.50
Generator output (kW)410.00
DutyPrime
Rating PrimePrime (PRP)
Average load factor for 24h– Maximum 80%
– Overload operation (<110%) is
limited to a maximum of 1 hour
per 12 hours
– Over 90% load operation limited
to a maximum of 3 hours per 24
hours
Overload+10% Overload
Installation locationIndoor

ENGINE DATA

Engine modelS6A3-PTAA
Engine speed (rpm)1800
Engine brake output (kWm)480.00
Turbocharged4 cycle, direct injection, turbocharged with air cooler
GovernorDigital Electrical type
Cooling methodCentrifugal type driven by engine
Starting methodStarter motor capacity : 7.5kW x 2 (DC24V)

SPECIFICATIONS

Generator set modelMGS0700R
Generator voltage (V)380
Frequency (Hz)60
Generator output (kVA)581.25
Generator output (kW)465.00
DutyCritical Power
Rating PrimeCritical Power (CP)
Average load factor for 24hMaximum 100%
OverloadNot available
Installation locationIndoor

ENGINE DATA

Engine modelS6A3-PTAA
Engine speed (rpm)1800
Engine brake output (kWm)536.00
Turbocharged4 cycle, direct injection, turbocharged with air cooler
GovernorDigital Electrical type
Cooling methodCentrifugal type driven by engine
Starting methodStarter motor capacity : 7.5kW x 2 (DC24V)

SPECIFICATIONS

Generator set modelMGS0700R
Generator voltage (V)380
Frequency (Hz)60
Generator output (kVA)537.50
Generator output (kW)430.00
DutyData Center Continuous Power
Rating PrimeData Center Continuous Power (DCCP)
Average load factor for 24h– Maximum 100%
– Overload (<110%) is limited to a maximum of 1
hour per 12 hours
Overload+10% Overload
Installation locationIndoor

ENGINE DATA

Engine modelS6A3-PTAA
Engine speed (rpm)1800
Engine brake output (kWm)480.00
Turbocharged4 cycle, direct injection, turbocharged with air cooler
GovernorDigital Electrical type
Cooling methodCentrifugal type driven by engine
Starting methodStarter motor capacity : 7.5kW x 2 (DC24V)

SPECIFICATIONS

Generator set modelMGS0700R
Generator voltage (V)480
Frequency (Hz)60
Generator output (kVA)581.25
Generator output (kW)465.00
DutyStandby
Rating PrimeStandby (ESP)
Average load factor for 24h– Maximum 80%
– 100% in emergency
OverloadNot available
Installation locationIndoor

ENGINE DATA

Engine modelS6A3-PTAA
Engine speed (rpm)1800
Engine brake output (kWm)536.00
Turbocharged4 cycle, direct injection, turbocharged with air cooler
GovernorDigital Electrical type
Cooling methodCentrifugal type driven by engine
Starting methodStarter motor capacity : 7.5kW x 2 (DC24V)

SPECIFICATIONS

Generator set modelMGS0800R
Generator voltage (V)380
Frequency (Hz)60
Generator output (kVA)775.00
Generator output (kW)620.00
DutyStandby
Rating PrimeStandby (ESP)
Average load factor for 24h– Maximum 80%
– 100% in emergency
OverloadNot available
Installation locationIndoor

ENGINE DATA

Engine modelS6R-PTAR
Engine speed (rpm)1800
Engine brake output (kWm)688.00
Turbocharged4 cycle, direct injection, turbocharged with air cooler
GovernorDigital Electrical type
Cooling methodCentrifugal type driven by engine
Starting methodStarter motor capacity : 7.5kW x 2 (DC24V)

SPECIFICATIONS

Generator set modelMGS0700R
Generator voltage (V)380
Frequency (Hz)60
Generator output (kVA)512.50
Generator output (kW)410.00
DutyPrime
Rating PrimePrime (PRP)
Average load factor for 24h– Maximum 80%
– Overload operation (<110%) is
limited to a maximum of 1 hour
per 12 hours
– Over 90% load operation limited
to a maximum of 3 hours per 24
hours
Overload+10% Overload
Installation locationIndoor

ENGINE DATA

Engine modelS6A3-PTAA
Engine speed (rpm)1800
Engine brake output (kWm)480.00
Turbocharged4 cycle, direct injection, turbocharged with air cooler
GovernorDigital Electrical type
Cooling methodCentrifugal type driven by engine
Starting methodStarter motor capacity : 7.5kW x 2 (DC24V)

SPECIFICATIONS

Generator set modelMGS0700R
Generator voltage (V)380
Frequency (Hz)60
Generator output (kVA)581.25
Generator output (kW)465.00
DutyCritical Power
Rating PrimeCritical Power (CP)
Average load factor for 24hMaximum 100%
OverloadNot available
Installation locationIndoor

ENGINE DATA

Engine modelS6A3-PTAA
Engine speed (rpm)1800
Engine brake output (kWm)536.00
Turbocharged4 cycle, direct injection, turbocharged with air cooler
GovernorDigital Electrical type
Cooling methodCentrifugal type driven by engine
Starting methodStarter motor capacity : 7.5kW x 2 (DC24V)

SPECIFICATIONS

Generator set modelMGS0700R
Generator voltage (V)380
Frequency (Hz)60
Generator output (kVA)537.50
Generator output (kW)430.00
DutyData Center Continuous Power
Rating PrimeData Center Continuous Power (DCCP)
Average load factor for 24h– Maximum 100%
– Overload (<110%) is limited to a maximum of 1
hour per 12 hours
Overload+10% Overload
Installation locationIndoor

ENGINE DATA

Engine modelS6A3-PTAA
Engine speed (rpm)1800
Engine brake output (kWm)480.00
Turbocharged4 cycle, direct injection, turbocharged with air cooler
GovernorDigital Electrical type
Cooling methodCentrifugal type driven by engine
Starting methodStarter motor capacity : 7.5kW x 2 (DC24V)

SPECIFICATIONS

Generator set modelMGS0700R
Generator voltage (V)480
Frequency (Hz)60
Generator output (kVA)512.50
Generator output (kW)410.00
DutyPrime
Rating PrimePrime (PRP)
Average load factor for 24h– Maximum 80%
– Overload operation (<110%) is
limited to a maximum of 1 hour
per 12 hours
– Over 90% load operation limited
to a maximum of 3 hours per 24
hours
Overload+10% Overload
Installation locationIndoor

ENGINE DATA

Engine modelS6A3-PTAA
Engine speed (rpm)1800
Engine brake output (kWm)480.00
Turbocharged4 cycle, direct injection, turbocharged with air cooler
GovernorDigital Electrical type
Cooling methodCentrifugal type driven by engine
Starting methodStarter motor capacity : 7.5kW x 2 (DC24V)

SPECIFICATIONS

Generator set modelMGS0700R
Generator voltage (V)480
Frequency (Hz)60
Generator output (kVA)581.25
Generator output (kW)465.00
DutyCritical Power
Rating PrimeCritical Power (CP)
Average load factor for 24hMaximum 100%
OverloadNot available
Installation locationIndoor

ENGINE DATA

Engine modelS6A3-PTAA
Engine speed (rpm)1800
Engine brake output (kWm)536.00
Turbocharged4 cycle, direct injection, turbocharged with air cooler
GovernorDigital Electrical type
Cooling methodCentrifugal type driven by engine
Starting methodStarter motor capacity : 7.5kW x 2 (DC24V)

SPECIFICATIONS

Generator set modelMGS0700R
Generator voltage (V)480
Frequency (Hz)60
Generator output (kVA)537.50
Generator output (kW)430.00
DutyData Center Continuous Power
Rating PrimeData Center Continuous Power (DCCP)
Average load factor for 24h– Maximum 100%
– Overload (<110%) is limited to a maximum of 1
hour per 12 hours
Overload+10% Overload
Installation locationIndoor

ENGINE DATA

Engine modelS6A3-PTAA
Engine speed (rpm)1800
Engine brake output (kWm)480.00
Turbocharged4 cycle, direct injection, turbocharged with air cooler
GovernorDigital Electrical type
Cooling methodCentrifugal type driven by engine
Starting methodStarter motor capacity : 7.5kW x 2 (DC24V)

Leading Diesel Generator Distributor in the Philippines of Mitsubishi MGS

As the certified diesel generator distributor in the Philippines, Kilton Motor Corporation brings world-class power solutions to the local market. The MGS series is designed by Mitsubishi Heavy Industries Engine System Asia (MHIES-A), adhering to refined Japanese engineering standards. To ensure peak performance and reliability, these units are manufactured in Singapore and Vietnam under the highest quality certifications (ISO 9001:2018).

Customizable Power Solutions for Every Industry

As your trusted genset supplier, Kilton Motor Corporation offers a versatile range of MGS units. We provide various combinations and additional options for customization, allowing us to fine-tune every diesel generator in the Philippines to meet your specific technical requirements.

Our generator sets are built for extreme durability, making them suitable for a wide array of demanding applications:

  • Construction & Industrial Usage

  • Healthcare & Hospital Facilities

  • Commercial & Municipal Buildings

  • Independent Power Plants (IPP)

  • Agriculture & Large-scale Factories

Certified Performance Standards

When you partner with a premier diesel generator distributor, you deserve guaranteed accuracy in power ratings. All MGS units distributed by Kilton comply with ISO8528-1 standards, ensuring reliable performance across all rating definitions:

  • Emergency Standby Power (ESP): Reliable backup for sudden outages.

  • Prime Rated Power (PRP): Powerful performance for variable load applications.

  • Continuous Operating Power (COP): Consistent energy for constant, long-term loads.

Kilton Motor Corporation combines Mitsubishi’s legendary Japanese reliability with local expertise, solidifying our position as the go-to genset supplier for robust power infrastructure in the Philippines.

Kilton Bldg., #6 Golden Mile Avenue,
Golden Mile Business Park, Brgy. Maduya, Carmona, Cavite, Philippines

Tel Nos:
+63 2 8889 1023 / +63 2 8844 5032
+63 2 8736 3650 /  +63 2 8844 5031
Telefax: +63 2 8889 1023

Sales Hotline: (SMS, Viber, WhatsApp)
+63 961 780 2771

Services and Parts Hotline:
(SMS, Viber, WhatsApp)

+63 922 838 2034 +63 917 534 0474
+63 961 780 2771 +63 28664 9996

Mitsubishi Generators

About MGS

Features

Performance

Performance

Resource Center

FAQ's

Brochures

Gallery

Case Studies

Kilton Motor

About Us

Services

Latest News

Kilton Bldg., #6 Golden Mile Avenue, Golden Mile Business Park, Brgy. Maduya, Carmona, Cavite, Philippines

Tel Nos:
+63 2 8889 1023 / +63 2 8844 5032
+63 2 8736 3650 /  +63 2 8844 5031 Telefax: +63 2 8889 1023

Sales Hotline: (SMS, Viber, WhatsApp)
+63 961 780 2771

Services and Parts Hotline: (SMS, Viber, WhatsApp)
+63 922 838 2034 +63 917 534 0474
+63 961 780 2771 +63 28664 9996

Resource Center

Gallery

Kilton Motor

© 2023 Created with Royal Elementor Addons